Building

Cables for security systems, intrusion detection, burglar alarm, and for the connection of video door phones, CCTV systems for access control. KNX BUS cables for building automation systems.

Download the catalog SECURITY 2015

Multicore fire resistant, halogen free (LSZH) cables FTE4OM1 UNI 9795: 2013 EN 50200 PH 120

STANDARD USE

Signalling, control cables for fixed installation in crowded areas with danger of fire (theaters, banks, stores, shops, multi-storey buildings, schools, hotels, airports, hospitals, etc.)

SPECIAL FEATURES

Fire resistant low smoke, zero halogen, cables for category 1(1) systems suitable to be installed in a single duct, without interposition of separator, with power cables with operating voltage up to 0,6/1 KV.

Data sheet
More info

Technical details:

Conductors

Stranded bare copper conductors
CEI 20-29 cl.5, EN 60228, IEC 60228 ref.

Insulation

Glass/Mica tape and halogen free crosslinked compound CEI 20-11, EN 50363-0 quality E4. Colour code: Red, Black.

Jacket

Special flame retardant, halogen free, low smoke compound CEI 20-11, EN 50363-0 quality M1, VDE 0207 HM2.
Colour: Red.

Elettrical resistance

0,50 mm2: < 39 Ohm/Km
0,75 mm2: < 26 Ohm/Km
1 mm2: < 19,5 Ohm/Km
1,5 mm2: < 13,3 Ohm/Km
2,5 mm2: < 7,98 Ohm/Km

Operating temperature

-25°C +90°C(posa fissa)

Bending radius

5 volte il diametro del cavo (posa fissa).

Operating voltage

100/100 V

Test voltage

2000 V

Fire resistance test

CEI 20-36/4-0 PH 30, CEI EN 50200 PH 120

Flame retardant test

CEI 20-35/1-2, EN 60332-1-2

Non-halogen verification

< 0,5 % (CEI 20-37/2-1, CEI EN 50267-2-1, IEC 60754-1)

Corrosivity of combustion gas

pH: > 4,3 - Conductivity: < 10 μS/mm (CEI 20-37/2-2, CEI EN 50267-2-2, IEC 60754-2)

Smoke density

Transmission of light: > 70% (CEI 20-37/3-1, EN 61034-2)

Toxicity index

< 2 (CEI 20-37/4-0)