Categories
DeviceNet PUR
STANDARD USE
Multicore double shielded cables for interconnection of industrial electronic appliances. Data pair and power supply pair integrated in one cable.
UL-CSA approval.
Technical details:
Conductors
Stranded tinned copper (Cu-ETP1)UL 1581, CEI 20-29 cl.5, VDE 0295 cl.5,
EN 60228, IEC 60228 ref.
Insulation
Polyolefin.Supply pair colour code: Red, Black.
Data pair colour code: Light Blue, White.
Shield on every single pair
Aluminium/polyester tape with aluminiumside in direct contact with braid
Overall Shield
Tinned copper braidwith stranded tinned copper drain wire.
Optical coverage: ≥ 85%.
Assembling
Non woven tape.Jacket
Low friction halogen free matt flame retardant Polyurethane, hydrolysis, microbial attack, abrasion, tear, oil resistantUL 1581 ref.
Colour code: Violet Ral 4001
Electrical Conductor Resistance
TRUNK 18AWG: < 23,2 Ohm/KmTRUNK 15AWG: < 11,3 Ohm/Km
DROP 24AWG: < 94,2 Ohm/Km
DROP 22AWG: < 59,4 Ohm/Km
Pair Capacitance
40 pF/mCharacteristic Impedance
120 OhmTransmission Rate
TRUNK:500 Kbit/s: fino a 200 m
250 Kbit/s: fino a 250 m
125 Kbit/s: fino a 500 m
DROP:
125÷500 Kbit/s: fino a 100 m
Operating Voltage
30 VOperating Temperature
Dynamic application: -40°C + 80°CBending radius
6 times overall diameter of cable.Flame retardant test
CEI 20-35/1-2, EN 60332-1-2, IEC 60332-1-2 UL 1581 cable flame test, FT1 test.Non-Halogen Verification
< 0,5 % (CEI 20-37/2-1, CEI EN 50267-2-1, IEC 60754-1)UL-CSA Approval (E235078)
AWM Style 20236 80°C 30 V – CSA I/II A/B 80°C 30 V FT1AWM Style 20554 80°C 30 V - CSA I/II A/B 80°C 30 V FT1
SISTEMA / SYSTEM | CODICE / CODE | FORMAZIONE / TYPE | Ø ESTERNO / OUTER Ø ±5% (mm) | PESO MEDIO / AVERAGE WEIGHT (kg/km) |
---|---|---|---|---|
DROP | [(2x24AWG)SN+(2x22AWG)SN]ST | 7,2 | 60 | |
TRUNK | [(2x18AWG)SN+(2x15AWG)SN]ST | 11,0 | 180 |