Fire resistant LSZH cables complying with CEI 20-36, IEC 60331, EN 50200 PH 60-90-120 for fire detection systems

STANDARD USE

Fire resistant LSZH (low smoke zero halogen) cables suitable for fire alarm systems and emergency lighting circuits

ON REQUEST

braid armour

Data sheet
More info

Technical details:

Conductors

Stranded bare copper conductors
CEI 20-29 cl.5, EN 60228, IEC 60228 ref.

Insulation

Glass/Mica tape and halogen free crosslinked compound
CEI 20-11 quality G10, VDE 0207/23 HJ1.
Colour code: differently coloured.

Jacket

Special flame retardant, halogen free, low smoke compound CEI 20-11, EN 50363-0 quality M1, VDE 0207 HM2.
Colour: Red.

Elettrical resistance

0,50 mm2: < 39 Ohm/Km
0,75 mm2: < 26 Ohm/Km
1 mm2: < 19,5 Ohm/Km
1,5 mm2: < 13,3 Ohm/Km
2,5 mm2: < 7,98 Ohm/Km

Operating temperature

-25°C +90°C(fixed laying)

Bending radius

5 times overall diameter of cable (fixed laying).

Operating voltage

450/750 V
0,6/1 kV

Test voltage

450/750 V: 3000 V
0,6/1 kV: 4000 V

Fire resistance test

CEI 20-36/4-0 PH 60, PH 90, PH 120
CEI EN 50200 PH 60, PH 90, PH 120

Flame retardant test

CEI 20-35/1-2, EN 60332-1-2, IEC 60332-1-2


No Flame Propagation Test

CEI 20-22/3, EN 60332-3-24 cat.C, IEC 60332-3-24 cat.C

Non-halogen verification

< 0,5 % (CEI 20-37/2-1, CEI EN 50267-2-1, IEC 60754-1)

Corrosivity of combustion gas

pH: > 4,3 - Conductivity: < 10 μS/mm (CEI 20-37/2-2, CEI EN 50267-2-2, IEC 60754-2)

Smoke density

Transmission of light: > 70% (CEI 20-37/3-1, EN 61034-2)

Toxicity index

< 2 (CEI 20-37/4-0)

Armour

Zinc coated steel braid
or stainless steel braid.