Fire resistant LSZH shielded cables complying with CEI 20-36, IEC 60331, EN 50200 PH 60-90-120 for fire detection systems
Fire resistant LSZH shielded cables complying with CEI 20-36, IEC 60331, EN 50200 PH 60-90-120 for fire detection systems.
STANDARD USE
fire resistant LSZH (low smoke zero halogen) cables suitable for fire alarm systems and emergency lighting circuits.
ON REQUEST
braid armour.
Data sheet More infoTechnical details:
Conductors
Stranded bare copper conductorsCEI 20-29 cl.5, EN 60228, IEC 60228 ref.
Insulation
Glass/Mica tape and halogen free crosslinked compound CEI 20-11, EN 50363-0 quality E4.Colour code: differently coloured.
Shield
Aluminium/polyester tape helically wound with stranded tinned copper drain wire.Jacket
Special flame retardant, halogen free, low smoke compound CEI 20-11, EN 50363-0 quality M1, VDE 0207 HM2.Colour: Red.
Electrical Resistance
0,50 mm2: < 39 Ohm/Km0,75 mm2: < 26 Ohm/Km
1 mm2: < 19,5 Ohm/Km
1,5 mm2: < 13,3 Ohm/Km
2,5 mm2: < 7,98 Ohm/Km
Operating Temperature
-25°C +90°C(fixed laying)Bending Radius
5 times overall diameter of cable (fixed laying).Operating Voltage
450/750 V0,6/1 kV
Test Voltage
450/750 V: 3000 V0,6/1 kV: 4000 V
Fire Resistance Test
CEI 20-36/4-0 PH 60,PH 90, PH 120CEI EN 50200 PH 60, PH 90, PH 120
Flame Retardant Test
CEI 20-35/1-2, EN 60332-1-2, IEC 60332-3-24 cat.CNo Flame Propagation Test
CEI 20-22/3, EN 60332-3-24 cat.C, IEC 60332-3-24 cat.CNon-Halogen Verification
< 0,5 % (CEI 20-37/2-1, CEI EN 50267-2-1, IEC 60754-1)Corrosivity of Combustion of Gas
pH: > 4,3 - Conductivity: < 10 μS/mm(CEI 20-37/2-2, CEI EN 50267-2-2, IEC 60754-2)
Smoke Density
Transmission of light: > 70% (CEI 20-37/3-1, EN 61034-2)Toxicity Index
< 2 (CEI 20-37/4-0)Armour
Zinc coated steel braidor stainless steel braid.