Automation

STATIC APPLICATION

PVC Twisted Pair Shielded Cables

STANDARD USE

Twisted pair shielded control cables for static applications in industrial environments, with small external dimensions, high flexibility and good resistance to industrial oils,
UL-CSA approval.

Data sheet
More info

Technical details:

Conductors

Flexible stranded bare copper (Cu-ETP1)
CEI 20-29 cl.5, VDE 0295 cl.5, EN 60228, IEC 60228 ref.
Cross sect. area (mm2): from 0,14 to 0,50.

Insulation

Polyolefin (PE, PP) UL 1581 ref.
Colour code: DIN 47100

Assembling

Protective tape

Overall Shield

Tinned copper braid.
Optical coverage: ≥ 85%

Assembling

Non woven tape

Jacket

Flame retardant and oil resistant Polyvinylchloride (PVC)
UL 1581, CEI 20-11 cl. TM2, EN 50363 ref.
Colour code:
Grey Ral 7001 (other colours on request)

Operating Voltage

300 V

Test Voltage

2000 V

Operating Temperature

-15°C +80°C

Bending radius

7,5 times overall diameter of cable.

Flame retardant test

CEI 20-35/1-2, EN 60332-1-2, IEC 60332-1-2, UL cable flame test, FT1 test

UL-CSA Approval (E235078)

AWM STYLE 2464 – CSA I/II A/B 80°C 300 V FT1
CODICE / CODEFORMAZIONE / TYPEØ ESTERNO / OUTER Ø ±5% (mm)PESO MEDIO / AVERAGE WEIGHT (kg/km)
2x2x0,145,135
3x2x0,145,637
4x2x0,146,045
5x2x0,146,752
6x2x0,147,260
8x2x0,147,680
10x2x0,149,091
16x2x0,149,6130
2x2x0,255,945
3x2x0,256,649
4x2x0,257,060
5x2x0,257,581
6x2x0,257,981
8x2x0,258,6125
10x2x0,2510,0133
16x2x0,2511,3186
2x2x0,346,252
3x2x0,347,158
4x2x0,347,670
5x2x0,348,383
6x2x0,348,899
8x2x0,349,4145
10x2x0,3410,7156
16x2x0,3412,1227
2x2x0,506,960
3x2x0,507,983
4x2x0,508,4102
5x2x0,509,3123
6x2x0,5010,2146
8x2x0,5011,6184